● Large discharge capacity and long service life;
● Multi-stage protection with low residual voltage and excellent protection effect;
● Low insertion loss and superior transmission performance;
● Built-in fast semiconductor protection components with nanosecond-level response speed;
● Energy-saving, eco-friendly and easy to install;
● Multi-channel network surge protectors are optional: 4-channel, 8-channel, 12-channel, 16-channel, 24-channel, etc.
LYX-N multi-channel network surge protectors are designed, manufactured and tested in accordance with international standard IEC61643.21 and national standard GB18802.21. LYX-N network signal surge protectors are mainly used to protect equipment from surge overvoltage and overcurrent intruding along network signal lines, such as network switches, servers, routers, MODEMs, network terminals, etc. The interface type of the surge protector is generally RJ45 interface.
| Model | LYX-N |
| Specification | 24-channel 100M network signal |
| Operating Voltage (V) | 5V |
| Maximum Continuous Operating Voltage Uc (V) | 8V |
| Nominal Discharge Current In (8/20μs) (kA) | 5kA |
| Maximum Discharge Current Imax (8/20μs) (kA) | 10kA |
| Voltage Protection Level (V) | ≤15V |
| Response Time (ns) | ≤1 ns |
| Transmission Rate (Mbit/s) | 1000M |
| Insertion Loss (dB) | ≤0.2dB |
| Input Impedance (Ω) | ≤2Ω |
| Protected Pins | 1-8 |
| Interface Type | RJ45 24-port |
| Housing Material | Aluminum housing |
| Protection Class, conform to IEC 60529/EN 60529 | IP20 |
| Dimensions (mm) | 19-inch standard rack-mounted |
● This product adopts two-port series connection.
● Please select a product with the same interface type as the protected equipment.
● "IN" of the surge protector is for input, "OUT" is for output. The output terminal is connected to the input end of the protected equipment.
● The PE wire of the surge protector must be reliably connected to the grounding wire of the lightning protection system. The grounding wire is generally 1.5-2.5mm², and the connecting wire should be short, thick and straight.
● During the use of the surge protector, regular inspection is required. If any fault occurs, repair or replace it in time to ensure equipment safety.
● Lightning protection grounding shall comply with lightning protection specifications, and the grounding resistance shall be less than 10Ω.