● LYX1-RJ11: Small loop cross-section, low inductive voltage drop, dual overvoltage and overload protection, shielded aluminum metal housing.
● LYX1-RJ45: Equipped with RJ45 male/female connectors for input and output, convenient connection and simple installation. It features small loop cross-section, low inductive voltage drop, dual overvoltage and overload protection, and shielded aluminum metal housing.
● LYX1-RJ11 Series Signal Surge Protective Device (SPD): Suitable for circuits such as Modems, DDN leased lines, fax machines, telephones, etc., to protect signal equipment from damage caused by indirect or direct lightning effects and network overvoltages.
● LYX1-RJ45 Series Signal Surge Protective Device (SPD): Suitable for computers, routers, Hubs and other equipment, providing protection for RJ45 interfaces and their internal circuits. Its coarse, fine and ultra-fine protection functions can meet different surge protection intervals, preventing damage to signal equipment caused by ground potential rise or line induced overvoltage.
| Model & Specification | LYX1-RJ11 | LYX1-RJ45 | LYX1-RJ45 | ||
| DC110 | DD5 | ED5 | DD12 | ED12 | |
| Rated Voltage Un (V) | DC110 | DC5 | DC12 | ||
| Maximum Continuous Operating Voltage Uc (V) | DC150 | DC6 | DC15 | ||
| Voltage Protection Level Up (V)< | 500 | 40 | 60 | ||
| Maximum Discharge Current (8/20μs) | 5kA | ||||
| Nominal Discharge Current In (8/20μs)(kA) | 3kA | ||||
| Bandwidth | 2MHz | 100MHz | |||
| Insertion Loss | ≤0.5dB | ≤0.3dB | |||
| Protected Lines | 3,4 | 1,2,3,6 | |||
| Response Time (ns) | <1 | <1 | |||
| Failure Mechanism | Communication line short-circuited to ground or disconnected | Communication line short-circuited to ground or disconnected | |||
● Installed at RJ11/RJ45 interfaces between LPZ1 and LPZ3 for data lines.
● For RJ11 interface installation, multi-pole or multi-loop signal surge protectors can be configured according to user requirements.