● Aluminum alloy housing for easy installation and replacement.
● Built-in temperature-controlled circuit breaking technology and multi-protection technology, featuring strong protection capability and high reliability.
● Green indicator light on for normal surge protection, off for fault status, clear and easy to identify.
● Provides multiple protection functions: power supply and network signal.
● 48V DC power interface can be installed according to user requirements.
LYX-POE is suitable for lightning protection of network equipment powered by Cat5e Ethernet cables. It is designed to be installed at the interface between lightning protection zones LPZ1-LPZ3, featuring two-stage protection to ensure network equipment is protected from damage caused by overvoltages and overcurrents induced by lightning, industrial interference, etc. It is widely used for lightning protection of network equipment such as wireless bridges and IP cameras powered by Ethernet cables.
| Model & Specification | LYX-POE | ||
| Signal | Rated Operating Voltage Un (DC) V | 5 | |
| Maximum Continuous Operating Voltage Uc (DC) V | 8 | ||
| Nominal Discharge Current In (8/20μs) kA | 3 | ||
| Maximum Discharge Current Imax (8/20μs) kA | 5 | ||
| Impulse Protection Voltage (1kV/μs) | Line-Line | ≤60 | |
| Line-Ground | ≤500 | ||
| Transmission Rate | 100M bps | ||
| Insertion Loss | 0.5dB | ||
| Protected Lines | 1, 2, 3, 6 | ||
| Power | Rated Operating Voltage Un (DC) V | 48 | |
| Maximum Continuous Operating Voltage Uc (DC) V | 60 | ||
| Nominal Discharge Current In (8/20μs) kA | 3 | ||
| Maximum Discharge Current Imax (8/20μs) kA | 5 | ||
| Voltage Protection Level Up V | Line-Line | ≤350 | |
| Line-Ground | ≤500 | ||
| Protected Lines | 4, 5, 7, 8 | ||
| Housing Material | Aluminum Alloy | ||
● The product is connected in series at the input front end of the protected equipment.
● During installation, the lightning protection grounding wire of the product shall be directly connected to the lightning protection grounding grid of the equipment room. The grounding shall be reliable, and the length of the grounding wire shall be less than 0.5m.
● No special maintenance is required for this product. The green light is on continuously when the 48V DC power supply is normal, and it goes out in case of failure. At this time, remove the SPD to check whether the input power supply is normal. If the input power supply is normal, it indicates that the SPD is damaged and should be replaced immediately.