● This product is a single-port, indoor fixed-installation voltage switching type SPD. It is designed in accordance with current national standards such as GB50057-2010 and GB18802.1. It features high impulse current (Iimp: 30kA) and low residual voltage (Up: 2.5kV). Its core components consist of multi-stage graphite gaps. Through reasonable design and precise processing, the spark gaps are integrated to form a sealed structure, ensuring the safe distance inside the spark gaps. No arc leakage will occur even when surge current passes through, so no special space for arc leakage is required during installation. The product quality is stable and reliable.
● The product is installed at the junction of LPZ0A / LPZ0B zone and LPZ1 zone, or at the main distribution box (cabinet) for power incoming, mounted on 35mm standard DIN rail. Connecting wires adopt 6~35mm² multi-strand copper flexible cables.
● The grounding wire shall use bicolor wires with cross-section ≥16mm² and length ≤500mm.
● To prevent the failure of surge protective devices from affecting the safe operation of the power grid, a matching LYSCB backup protector shall be connected in series with the protector connected to the L line.
LYD1-I30 Lightning Surge Protective Device (hereinafter referred to as SPD) is suitable for TT, TN and other power supply systems with AC 50/60Hz, 420V and below, providing protection against lightning strikes or other transient overvoltages. It is applied to Class I (Class B) lightning protection of power supply systems in areas with high lightning risk, installed at the junction of LPZ0B zone and LPZ1 zone. All technical indicators meet the requirements specified in the current GB50057-2010 and GB18802.1 standards.
| Item | LYD1-I30 | |
| Lightning Protection Zone | Class I | |
| Maximum Continuous Operating Voltage Uc (V) | 255 | 420 |
| Voltage Protection Level (8/20μs) Up (kV) | 2.5 | 2.5 |
| Maximum Impulse Current Iimp (10/350μs) (kA) | 30 | 30 |
| Nominal Discharge Current In (8/20μs) (kA) | 30 | 30 |
| Response Time (ns) | ≤100 | ≤100 |
| Ambient Temperature | -40℃~+80℃ | -40℃~+80℃ |
| Protection Class | IP20 | IP20 |
| Failure Indication | White for Normal, Red for Failure | White for Normal, Red for Failure |
| Remote Signal Contact | Optional Accessory | Optional Accessory |
| Installation | Mounted on 35mm DIN Rail | Mounted on 35mm DIN Rail |
The enclosure size of the LYD1-130 lightning surge protector meets the requirement of 36mm width module, making the device easy to install. It can be quickly installed by snapping onto a 35mm DIN rail.