LYD1-I30 Surge Protective Device (SPD)

● This product is a single-port, indoor fixed-installation voltage switching type SPD. It is designed in accordance with current national standards such as GB50057-2010 and GB18802.1. It features high impulse current (Iimp: 30kA) and low residual voltage (Up: 2.5kV). Its core components consist of multi-stage graphite gaps. Through reasonable design and precise processing, the spark gaps are integrated to form a sealed structure, ensuring the safe distance inside the spark gaps. No arc leakage will occur even when surge current passes through, so no special space for arc leakage is required during installation. The product quality is stable and reliable.

● The product is installed at the junction of LPZ0A / LPZ0B zone and LPZ1 zone, or at the main distribution box (cabinet) for power incoming, mounted on 35mm standard DIN rail. Connecting wires adopt 6~35mm² multi-strand copper flexible cables.

● The grounding wire shall use bicolor wires with cross-section ≥16mm² and length ≤500mm.

● To prevent the failure of surge protective devices from affecting the safe operation of the power grid, a matching LYSCB backup protector shall be connected in series with the protector connected to the L line.

 
获取报价

产品概述

LYD1-I30 Lightning Surge Protective Device (hereinafter referred to as SPD) is suitable for TT, TN and other power supply systems with AC 50/60Hz, 420V and below, providing protection against lightning strikes or other transient overvoltages. It is applied to Class I (Class B) lightning protection of power supply systems in areas with high lightning risk, installed at the junction of LPZ0B zone and LPZ1 zone. All technical indicators meet the requirements specified in the current GB50057-2010 and GB18802.1 standards.

技术参数

ItemLYD1-I30
Lightning Protection ZoneClass I
Maximum Continuous Operating Voltage Uc (V)255420
Voltage Protection Level (8/20μs) Up (kV)2.52.5
Maximum Impulse Current Iimp (10/350μs) (kA)3030
Nominal Discharge Current In (8/20μs) (kA)3030
Response Time (ns)≤100≤100
Ambient Temperature-40℃~+80℃-40℃~+80℃
Protection ClassIP20IP20
Failure IndicationWhite for Normal, Red for FailureWhite for Normal, Red for Failure
Remote Signal ContactOptional AccessoryOptional Accessory
InstallationMounted on 35mm DIN RailMounted on 35mm DIN Rail