● The intelligent SPD integrates the SPD and detection module, specially designed for online monitoring of SPD degradation, grounding status of SPD and Surge Circuit Breaker (SCB), and SPD operation counts (lightning strike counts).
● It features online detection, no self-check required, and real-time monitoring. Data is transmitted via RS485 wired communication to realize remote online monitoring, and it adopts 35mm DIN rail mounting design.
● The monitoring module conducts online monitoring of SPD operation and triggers an alarm within seconds when the SPD operates. It also monitors the SPD degradation status online and gives an alarm within seconds if any abnormality occurs.
● The monitoring module can be connected to a background server. Within the network coverage, computers and smartphones can remotely monitor the status of any SPD.
● The product adopts industrial-grade design with high precision, stability and reliability. The monitoring software supports 24/7 uninterrupted online monitoring, automatically stores recorded data and generates reports, facilitating historical query and analysis of SPD status changes at monitoring points.
LYD1 Series Intelligent Surge Protective Device (Intelligent SPD) is a high-tech product independently developed by our company for "on-line monitoring of lightning protection". Intelligent SPD is suitable for power distribution systems in power, railway transportation, airports and ports, petrochemical, new energy, communications, environmental protection, water conservancy and other industries, realizing real-time monitoring of the operating status of users and Surge Protective Devices (SPD). The product complies with GB18802.1-2011, IEC61643-1 and other standards.
● SPD Degradation Monitoring: Monitors the signal of the SPD remote signal terminal, collects the signal uninterruptedly through its own acquisition system, and the system alarms within seconds when the signal is disconnected.
● Circuit Breaker / SPD Grounding Monitoring: Real-time monitoring of the open/closed status of the circuit breaker. The system alarms within seconds when the circuit breaker is open or when the SPD loses grounding.
● Lightning Strike Count Monitoring: Composed of built-in current sensor, signal processing circuit and electromagnetic counter. The current sensor is close to the grounding wire of the SPD. The induced current signal drives the electromagnetic counter to record the number of lightning strikes after amplitude limiting, rectification and filtering.
● L - 220V Live Wire
● N - 220V Neutral Wire
● KL - Circuit Breaker Monitoring Terminal L
● KN - Circuit Breaker Monitoring Terminal N / SPD Grounding Terminal
● Reset - Reset the lightning strike count displayed on the digital tube
● RS485+, RS485-, GND - For Communication
| Model & Specification | LYD1 |
| Functions | Collect 1-channel SPD remote signal, 1-channel circuit breaker/SPD grounding status, 1-channel SPD operation counts |
| Power Supply | AC220V |
| Surge Protection Capacity Imax (8/20μs) | Up to 80kA |
| SPD Remote Signal Monitoring | 1-channel built-in signal interface |
| Circuit Breaker/Grounding Status Monitoring | 1-channel for judging SPD normal operation or proper grounding |
| Lightning Strike Counting | 1-channel (0-99) built-in sensor |
| Operating Current for Lightning Counting | ≥300A |
| Networking | Flexible networking |
| Protocol | Custom protocol |
| Communication Mode | RS-485 |
| Mounting Method | 35mm DIN rail |
| Operating Temperature | -20℃~+60℃ |
| Storage Temperature | -20℃~+70℃ |
| Alarm Function | SPD remote signal & operation counts: with alarm; Circuit breaker tripping: with alarm |
| Protection Class | IP20 |
| Installation Requirements | Installed in rainproof and waterproof environment |
| Power Supply Mode | External power supply |
Indicator Lights
| Item | Description |
| Power Indicator | Operating status indicator, always on when power is connected |
| Circuit Breaker/Grounding Alarm | Off in normal operation; flashes when circuit breaker trips or grounding fails |
| Remote Signal Alarm | Off in normal status; flashes when alarm is triggered |
| Lightning Strike Counts | 2-digit digital tube display |