1776331048233354.jpg
1776331048233354.jpg

LYSCB Surge Backup Protector (SCB)

● Realizes selective control and tripping mechanism breaking through current parameter variation;

● Low residual voltage under impulse current, with test performance superior to circuit breakers and fuses;

● Adopts high-energy materials to solve the service life issue of the product;

● The product can be used with three types of SPD: T1, T2 and T3;

● Mounted on 35mm DIN rail for use;

● Remote control alarm is optional;

 
获取报价

产品概述

● LYSCB surge backup protector is a specially developed product that provides backup protection solutions for SPD. It eliminates the potential safety hazards when using circuit breakers or fuses as SPD backup protection.

● LYSCB is suitable for TT, TN and other power supply systems of 50/60Hz and below 400V. It features no false tripping when lightning current passes through, rapid current cut-off in case of SPD breakdown and short circuit, and low residual voltage under impulse current. The product complies with GB18802.1-2011, IEC61643-11-2011 and other standards.

技术参数

Model & SpecificationLYSCB15LYSCB80LYSCB60LYSCB40LYSCB20
Test CategoryT1T2T2T3T3
Rated Operating Voltage Ue230/400V AC230/400V AC230/400V AC230/400V AC230/400V AC
Maximum Impulse Current Imp15kA----
Maximum Discharge Current (8/20μs) Imax (kA)-80kA60kA40kA20kA
Nominal Discharge Current (8/20μs) In (kA)15kA40kA30kA20kA10kA
Matched SPD≤15kA(10/350μs)≤80kA(8/20μs)≤60kA(8/20μs)≤40kA(8/20μs)≤20kA(8/20μs)
Operating Frequency50/60Hz50/60Hz50/60Hz50/60Hz50/60Hz
Power Frequency Short-circuit Breaking Capacity Isc50kA50kA25kA25kA15kA
Power Frequency Short-circuit Operating Current3A3A3A3A3A
Power Frequency Breaking Time0.3s0.3s0.3s0.3s0.3s
Power Frequency Breaking Cycles1000 times1000 times1000 times1000 times1000 times
Remote IndicationIo accessory optionalIo accessory optionalIo accessory optionalIo accessory optionalIo accessory optional
Number of Poles1P,2P,3P,4P1P,2P,3P,4P1P,2P,3P,4P1P,2P,3P,4P1P,2P,3P,4P
Protection ClassIP20IP20IP20IP20IP20
Max. Wiring Cross-section6~25mm²6~25mm²6~25mm²6~25mm²6~25mm²
Operating Temperature-25℃~+60℃-25℃~+60℃-25℃~+60℃-25℃~+60℃-25℃~+60℃
Storage Temperature-40℃~+75℃-40℃~+75℃-40℃~+75℃-40℃~+75℃-40℃~+75℃
Remote Signaling FunctionOptional accessoryOptional accessoryOptional accessoryOptional accessoryOptional accessory


安装方式

外形尺寸图

2017雷源-2.png

在线留言

×